Ruck® smoke extractor roof fan horizontal
The new smoke roof fans from Ruck® are certified to temperature class F400 according to the European test standard DIN EN 12101-3 with certificate 1404-CPR-3027. This means that the DHN D F4 series is suitable for smoke and heat extraction up to 200°C in continuous operation and can briefly dissipate smoke and heat for up to 120 minutes in case of fire at a medium temperature of 400°C. In addition, the fan is very suitable for daily ventilation as required.
The DHN D F4 roof fans can be variably controlled by means of a frequency converter. This frequency converter can be found in the accessories listed below.The fan is used in cinemas, shopping malls, theatres and industrial buildings. The motor of the fan is located outside the air stream, so the polluted (greasy) air is not discharged via the motor.
Ventilationland.nl is a premium distributor of Ruck® fans and air handling units and therefore only at at Ventilationland do you get a 5-year warranty on all Ruck® fans.- F400 certified
- 200°C continuous operation
- 400°C for 120 minutes
- Motor outside the air stream
- Variable control with frequency converter
- Horizontal supply air pattern
It is possible to request a quote for orders with a minimum of 3 products and an ordervalue of £1000 (ex. VAT) or higher. This can be done via our request a quote page.
Brand | Ruck ventilatoren GmbH |
Category | Roof exhaust fan |
GTIN | 4061199030526 |
Manufacturer's item number | 150555 |
Article number | 65150555 |
Specifications
Number of phases | 3~ |
Number of poles | 2 |
Type of motor control | F |
Gewicht | 28.7 kg |
IP Motor | IP55 |
Insulation Class Motor | F |
Max. Operating Current | 2.3 A |
Max. pressure | 1240 Pa |
Max. Air Volume | 4525 m³/h |
Max. Current Consumption | 2.3 A |
Max. power consumption | 1145 W |
Max. Static Efficiency | 54.2 % |
Max. allowed Frequency (3˜ motors) | 50 Hz |
Max. allowed Medium Temperature | 200 °C |
Max. allowed Medium Temperature at Rated Current | 200 °C |
Max. allowed Ambient Temperature | 50 °C |
Max. allowed Ambient Temperature at Rated Current | 50 °C |
Max. number of revolutions | 2950 1/min |
Max. Total Efficiency | 55.1 % |
Min. Operating Temperature | -20 °C |
Motor type | 3~ |
Nominal frequency | 50 Hz |
Nominal power consumption | 1145 W |
Nominal voltage | 400 V |
Nominal current | 2.2 A |
Rated Speed | 2870 1/min |
Direction of blow out | Horizontal |