Free shipping from 100,-
100 day return period
Price Incl Vat

Maxivent WTW air handling units with counterflow heat exchanger, 700 m³/h, with electric heater on the left - PHE 700 F EOJL

Brand: Maxivent


Maxivent WTW air handling units with counterflow heat exchanger, 700 m³/h, with electric heater on the left - PHE 700 F EOJL
Maxivent WTW air handling units with counterflow heat exchanger, 700 m³/h, with electric heater on the left - PHE 700 F EOJL
Maxivent WTW air handling units with counterflow heat exchanger, 700 m³/h, with electric heater on the left - PHE 700 F EOJL
Maxivent WTW air handling units with counterflow heat exchanger, 700 m³/h, with electric heater on the left - PHE 700 F EOJL
-35%
RRP 9,429.22
6,129.00 -35%
You'll save 3300.22
Delivery time: 6 weeks
  • The largest collection in the United Kingdom
  • 100 day return period
  • Customer review 9/10
  • Safe shopping with Trustedshops

Pay safe and fast with:

  • Creditcard
  • PayPal
  • Apple Pay

Good points

  • Brand: Maxivent
  • Heat exchanger compliant with EN 308 and Eurovent-certified
  • Electric heating
  • Plug & Play Integrated Controller

Maxivent WTW Air Handling Units with Counterflow Heat Exchanger 700 m3/h with Left-Side Electric Heater - PHE 700 F EOJL

The Maxivent WTW air handling units with counterflow heat exchanger 700 m3/h with left-side electric heater - PHE 700 F EOJL is a high-quality, robust, and advanced balanced ventilation unit with heat recovery, specifically designed for offices, clinics, and small to medium-sized commercial buildings. The air handling unit has a maximum airflow of 870 m³/h and a thermal efficiency of 82%. The unit operates with a counterflow heat exchanger and EC fans and is equipped with an electric heater that ensures a stable and constant supply air temperature while preventing frost formation in the heat exchanger. The air handling unit is designed for ceiling mounting and can be opened from the bottom for maintenance.

Advantages and Features

  • Electric Heater: Integrated electric post-heating that prevents cold drafts and ensures a comfortable and stable supply air temperature, without the need for a hot water connection.
  • EC Fans: Direct-driven EC plug fans with high-efficiency electronic commutation (EC) provide an energy-efficient and quiet solution with low electricity consumption.
  • Counterflow Heat Exchanger: The integrated, efficient counterflow heat exchanger recovers 82% of the thermal energy from the exhaust air, without mixing air streams.
  • Panel Filter F7/M5: Ensures a high level of filtration of dust particles and pollutants from outside air, contributing to a healthy and comfortable indoor climate and protecting internal components.
  • Automatic Summer Bypass: Enables summer and night cooling by supplying cool outside air directly without warming in the heat exchanger.
  • Plug-and-Play Control: The air handling unit is delivered complete with built-in controls for all functions, allowing for quick and easy installation and commissioning without additional control equipment.

Applications and Use

The Maxivent WTW air handling units with counterflow heat exchanger 700 m3/h with left-side electric heater - PHE 700 F EOJL are designed for small to medium-sized commercial spaces such as offices, meeting rooms, clinics, retail stores, and educational or healthcare environments. Thanks to the combination of heat recovery, EC fans, and electric heating, the unit delivers stable and energy-efficient ventilation, even at low outdoor temperatures. The integrated control and summer bypass ensure a comfortable indoor climate year-round, both in winter and during warm periods.

Customising the WTW Unit

Are you interested in a customised model and want to learn more about the options? Please contact our sales department. They will be happy to discuss your requirements and assist you in configuring the ideal unit for your situation.

Brand Maxivent
Category Maxivent PHE Ceiling Units
GTIN 8719544341068
Manufacturer's item number 78010610
Article number 78010610

Specifications

Category code 36
Device emplacement Indoor positioning
Housing material Steel
Surface protection housing Continuously galvanised
Air volume, unloaded 604.8 m³/h
Supply filter according to ISO 16890-1:2016 ISO ePM1
Efficiency supply filter according to ISO 16890-1:2016 55 %
Heat recovery by Counter current unit
With bypass Yes
Type of cooling coil None
Type of heating coil Electrical heating element
Change-over system No
With humidifier No
Type of supply fan Direct
Exhaust filter according to ISO 16890-1:2016 ISO ePM10
Efficiency exhaust filter according to ISO 16890-1:2016 50 %
Type of exhaust fan Direct
Connection voltage 230 V
Power consumption 0.6 kW
With thermal overload protection Yes
Electrical connection Terminals
Suitable for electronic control Yes
Suitable for frequency control No
Suitable for transformer control No
Pole-reversible No
External controller required No
Frost protection circuit Yes
Type of motor Electronically commutated (EC)
Type of speed control Continuously variable
Number of connections suction side 2
Connection suction side Rectangular
Nominal duct height of suction end 200 mm
Nominal duct width of suction end 300 mm
Connection delivery side Rectangular
Number of connections delivery side 2
Nominal duct height, delivery side 200 mm
Nominal duct width, delivery side 300 mm
Degree of protection (IP) IP41
Explosion safety None
Max. air temperature 40 °C
Height 390 mm
Width 1000 mm
Length 1473 mm

Reviews