Free shipping from 100,-
100 day return period
Price Incl Vat

Maxivent WTW air handling units with counterflow heat exchanger, 4200 m³/h, with hot-water coil and cold-water coil, horizontal right-hand configuration - PHE 4200 H WKJR T 01

Brand: Maxivent


Maxivent WTW air handling units with counterflow heat exchanger, 4200 m³/h, with hot-water coil and cold-water coil, horizontal right-hand configuration - PHE 4200 H WKJR T 01
Maxivent WTW air handling units with counterflow heat exchanger, 4200 m³/h, with hot-water coil and cold-water coil, horizontal right-hand configuration - PHE 4200 H WKJR T 01
-35%
RRP 34,847.96
22,651.18 -35%
You'll save 12196.78
Delivery time: 6 weeks
  • The largest collection in the United Kingdom
  • 100 day return period
  • Customer review 9/10
  • Safe shopping with Trustedshops

Pay safe and fast with:

  • Creditcard
  • PayPal
  • Apple Pay

Good points

  • Brand: Maxivent
  • Heat exchanger compliant with EN 308 and Eurovent-certified
  • Hot-water faucet and cold-water faucet
  • Plug & Play Integrated Controller

Maxivent WTW Air Handling Units with Counterflow Heat Exchanger 4200 m³/h with Hot Water Coil and Chilled Water Coil Horizontal Right - PHE 4200 H WKJR T 01

The Maxivent WTW air handling units with counterflow heat exchanger 4200 m³/h featuring a hot water coil and chilled water coil, horizontal right - PHE 4200 H WKJR T 01, are high-quality, robust, and advanced balanced ventilation units with heat recovery, specially designed for offices, clinics, and medium to large commercial buildings. The air handling unit has a maximum airflow of 5180 m³/h and a thermal efficiency of 82%. The unit operates with a counterflow heat exchanger and EC fans, and is equipped with a hot water coil for heating and a chilled water coil for cooling the supply air. It is designed for floor mounting and can be opened on the right side for maintenance.

Benefits and Features

  • Hot Water Coil: Provides efficient and uniform heating of the supply air by utilising hot water from a central heating system or heat pump, resulting in a comfortable indoor climate and energy-efficient heat transfer.
  • Chilled Water Coil: Cools the supply air using chilled water from a cooling system, enabling energy-efficient and precisely controllable cooling of the room air.
  • EC Fans: Direct-driven EC plug fans with high-efficiency electronic commutation (EC) offer an energy-saving and quiet solution with low power consumption.
  • Counterflow Heat Exchanger: The integrated, efficient counterflow heat exchanger recovers 82% of the thermal energy from the exhaust air without mixing airflow streams.
  • Panel Filter F7/M5: Ensures a high level of filtration of dust particles and contaminants from outside air, contributing to a healthy and comfortable indoor environment and protecting internal components.
  • Automatic Summer Bypass: Allows summer and night cooling by supplying cool outside air directly without heating through the heat exchanger.
  • Plug-and-Play Control: The air handling unit is delivered complete with built-in control for all functions, enabling quick and easy installation and commissioning without the need for additional control technology.

Applications and Usage

The Maxivent WTW air handling units with counterflow heat exchanger 4200 m³/h with hot water coil and chilled water coil, horizontal right - PHE 4200 H WKJR T 01, are developed for medium to large commercial spaces such as offices, meeting rooms, clinics, retail stores, and educational or healthcare environments. Thanks to the combination of heat recovery, EC fans, hot water coil, and chilled water coil, the unit provides comprehensive and precisely controllable climate control throughout the year. The integrated control and summer bypass ensure a comfortable indoor climate year-round, both in winter and during hot periods.

Customising the WTW Unit

Are you interested in a customised model and want to learn more about the options? Please contact our sales department. They will be happy to advise you and help you configure the ideal unit for your situation.

Brand Maxivent
Category Maxivent PHE Counterflow - Side Connection
GTIN 8719544341532
Manufacturer's item number 78010657
Article number 78010657

Specifications

Category code 36
Length 2976 mm
Width 1380 mm
Height 1305 mm
Housing material Steel
Heat recovery by Counter current unit
Electrical connection Terminals
Type of motor Electronically commutated (EC)
Efficiency supply filter according to ISO 16890-1:2016 55 %
Degree of protection (IP) IP41
Efficiency exhaust filter according to ISO 16890-1:2016 50 %
With bypass Yes
Supply filter according to ISO 16890-1:2016 ISO ePM1
Exhaust filter according to ISO 16890-1:2016 ISO ePM10
Connection voltage 400 V
Surface protection housing Continuously galvanised
External controller required No
Device emplacement Indoor positioning
With thermal overload protection Yes
Type of speed control Continuously variable
Air volume, unloaded 3805.2 m³/h
Type of heating coil Hot water heat exchanger
Type of exhaust fan Direct
Power consumption 1.9 kW
Suitable for frequency control No
Frost protection circuit Yes
Pole-reversible No
Explosion safety None
Type of cooling coil Water/glycol
Suitable for transformer control No
Suitable for electronic control Yes
Type of supply fan Direct
Max. air temperature 40 °C
Change-over system No
With humidifier No
Nominal duct width of suction end 1000 mm
Connection suction side Rectangular
Nominal duct width, delivery side 1000 mm
Number of connections delivery side 2
Nominal duct height of suction end 500 mm
Connection delivery side Rectangular
Nominal duct height, delivery side 500 mm
Number of connections suction side 2

Documents

Documents

Reviews