- The largest collection in the United Kingdom
- 100 day return period
- Customer review 9/10
- Safe shopping with Trustedshops
Pay safe and fast with:
Good points
- Merk: Maxivent
- Warmtewisselaar EN 308 en Eurovent-gecertificeerd
- Warmwaterbatterij
- Plug & Play geïntegreerde controller
Maxivent WTW Air Handling Units with Counterflow Heat Exchanger 4200 m³/h with Horizontal Right Hot Water Coil - PHE 4200 H WOJR T 01
The Maxivent WTW air handling units with counterflow heat exchanger 4200 m³/h with horizontal right hot water coil - PHE 4200 H WOJR T 01 is a high-quality, robust, and advanced balanced ventilation unit with heat recovery, specifically designed for offices, medical practices, and medium to large commercial buildings. The air handling unit has a maximum airflow of 5430 m³/h and a thermal efficiency of 82%. The unit operates with a counterflow heat exchanger and EC fans, and is equipped with a hot water coil that heats the supply air to the desired temperature and helps prevent frost formation in the heat exchanger. The air handling unit is designed for floor mounting and can be opened on the right side for maintenance.
Advantages and Features
- Hot Water Coil: Provides efficient and even heating of the supply air by utilising hot water from a central heating system or heat pump, resulting in a comfortable indoor climate and energy-efficient heat transfer.
- EC Fans: Direct-driven EC plug fans with high-efficiency electronically commutated (EC) motors offer an energy-saving and quiet solution with low electricity consumption.
- Counterflow Heat Exchanger: The integrated, efficient counterflow heat exchanger recovers 82% of the thermal energy from the exhaust air without mixing air streams.
- Panel Filter F7/M5: Ensures a high level of filtration of dust particles and contaminants from outside air, contributing to a healthy and comfortable indoor climate and protecting internal components.
- Automatic Summer Bypass: Enables summer and night cooling by supplying cool outside air directly without warming in the heat exchanger.
- Plug-and-Play Control: The air handling unit is delivered complete with built-in controls for all functions, making installation and commissioning quick and straightforward without additional control technology.
Applications and Use
The Maxivent WTW air handling units with counterflow heat exchanger 4200 m³/h with horizontal right hot water coil - PHE 4200 H WOJR T 01 have been developed for medium to large commercial spaces such as offices, meeting rooms, medical practices, retail stores, and educational or healthcare environments. Thanks to the combination of heat recovery, EC fans, and the hot water coil, the unit provides stable and energy-efficient ventilation, even at low outdoor temperatures. The integrated control and summer bypass ensure the indoor climate remains comfortable all year round, both in winter and during warm spells.
Customising the WTW Unit
Are you interested in a customised model and would like to know more about the options available? Please contact our sales department. They will be happy to assist you and help design the ideal unit for your specific requirements.
| Brand | Maxivent |
| Category | Maxivent PHE Counterflow - Side Connection |
| GTIN | 8719544341518 |
| Manufacturer's item number | 78010655 |
| Article number | 78010655 |
Specifications
| Category code | 36 |
| Length | 2976 mm |
| Width | 1380 mm |
| Height | 1305 mm |
| Housing material | Steel |
| Heat recovery by | Counter current unit |
| Electrical connection | Terminals |
| Type of motor | Electronically commutated (EC) |
| Efficiency supply filter according to ISO 16890-1:2016 | 55 % |
| Degree of protection (IP) | IP41 |
| Efficiency exhaust filter according to ISO 16890-1:2016 | 50 % |
| With bypass | Yes |
| Supply filter according to ISO 16890-1:2016 | ISO ePM1 |
| Exhaust filter according to ISO 16890-1:2016 | ISO ePM10 |
| Connection voltage | 400 V |
| Surface protection housing | Continuously galvanised |
| External controller required | No |
| Device emplacement | Indoor positioning |
| With thermal overload protection | Yes |
| Type of speed control | Continuously variable |
| Air volume, unloaded | 3841.2 m³/h |
| Type of heating coil | Hot water heat exchanger |
| Type of exhaust fan | Direct |
| Power consumption | 1.84 kW |
| Suitable for frequency control | No |
| Frost protection circuit | Yes |
| Pole-reversible | No |
| Explosion safety | None |
| Type of cooling coil | None |
| Suitable for transformer control | No |
| Suitable for electronic control | Yes |
| Type of supply fan | Direct |
| Max. air temperature | 40 °C |
| Change-over system | No |
| With humidifier | No |
| Nominal duct width of suction end | 1000 mm |
| Connection suction side | Rectangular |
| Nominal duct width, delivery side | 1000 mm |
| Number of connections delivery side | 2 |
| Nominal duct height of suction end | 500 mm |
| Connection delivery side | Rectangular |
| Nominal duct height, delivery side | 500 mm |
| Number of connections suction side | 2 |