- The largest collection in the United Kingdom
- 100 day return period
- Customer review 9/10
- Safe shopping with Trustedshops
Pay safe and fast with:
Good points
- Brand: Maxivent
- Heat exchanger compliant with EN 308 and Eurovent-certified
- DX battery
- Plug & Play Integrated Controller
Maxivent WTW Air Handling Units with Counterflow Heat Exchanger 2800 m³/h with DX Coil Horizontal Right - PHE 2800 H ODJR
The Maxivent WTW air handling units with counterflow heat exchanger 2800 m³/h with DX coil horizontal right - PHE 2800 H ODJR are high-quality, robust, and advanced balanced ventilation units with heat recovery, specifically designed for offices, practices, and small to medium-sized commercial buildings. The AHU has a maximum airflow of 3440 m³/h and a thermal efficiency of 84%. The unit operates with a counterflow heat exchanger and EC fans and features an integrated DX coil that can both heat and cool the supply air. The air handling unit is designed for floor mounting and can be opened on the right side for maintenance.
Advantages and Features
- DX Coil (Heating and Cooling): Direct expansion unit that handles both heating and cooling of the supply air via a single integrated system, simplifying installation and providing high comfort under varying outdoor temperatures.
- EC Fans: Direct-driven EC plug fans with high-efficiency electronic commutation (EC) offer an energy-efficient and quiet solution with low electricity consumption.
- Counterflow Heat Exchanger: The integrated, efficient counterflow heat exchanger recovers 84% of the thermal energy from the exhaust air, without mixing air streams.
- Panel Filter F7/M5: Ensures a high degree of filtration of dust particles and contaminants from the outdoor air, contributing to a healthy and comfortable indoor climate and protecting internal components.
- Automatic Summer Bypass: Enables summer and night cooling by supplying cool outdoor air directly without heating through the heat exchanger.
- Plug-and-Play Control: The AHU is delivered complete with built-in control for all functions, allowing for quick and easy installation and commissioning without additional control equipment.
Applications and Use
The Maxivent WTW air handling units with counterflow heat exchanger 2800 m³/h with DX coil horizontal right - PHE 2800 H ODJR are designed for small to medium-sized commercial spaces such as offices, meeting rooms, medical practices, retail stores, and educational or healthcare environments. Thanks to the combination of heat recovery, EC fans, and the integrated DX coil, the unit provides both heating and cooling in a compact and energy-efficient manner. The integrated control and summer bypass ensure the indoor climate remains comfortable year-round, both in winter and during warm periods.
Customising the WTW Unit
Interested in a customised model or want to learn more about the options? Please contact our sales department. They will be happy to assist you and help tailor the ideal unit for your specific needs.
| Brand | Maxivent |
| Category | Maxivent PHE Counterflow - Side Connection |
| GTIN | 8719544341488 |
| Manufacturer's item number | 78010652 |
| Article number | 78010652 |
Specifications
| Category code | 36 |
| Device emplacement | Indoor positioning |
| Housing material | Steel |
| Surface protection housing | Continuously galvanised |
| Air volume, unloaded | 2631.6 m³/h |
| Supply filter according to ISO 16890-1:2016 | ISO ePM1 |
| Efficiency supply filter according to ISO 16890-1:2016 | 55 % |
| Heat recovery by | Counter current unit |
| With bypass | Yes |
| Type of cooling coil | DX (direct expansion) |
| Type of heating coil | DX (direct expansion) |
| Change-over system | No |
| With humidifier | No |
| Type of supply fan | Direct |
| Exhaust filter according to ISO 16890-1:2016 | ISO ePM10 |
| Efficiency exhaust filter according to ISO 16890-1:2016 | 50 % |
| Type of exhaust fan | Direct |
| Connection voltage | 400 V |
| Power consumption | 1.35 kW |
| With thermal overload protection | Yes |
| Electrical connection | Terminals |
| Suitable for electronic control | Yes |
| Suitable for frequency control | No |
| Suitable for transformer control | No |
| Pole-reversible | No |
| External controller required | No |
| Frost protection circuit | Yes |
| Type of motor | Electronically commutated (EC) |
| Type of speed control | Continuously variable |
| Number of connections suction side | 2 |
| Connection suction side | Rectangular |
| Nominal duct height of suction end | 400 mm |
| Nominal duct width of suction end | 600 mm |
| Connection delivery side | Rectangular |
| Number of connections delivery side | 2 |
| Nominal duct height, delivery side | 400 mm |
| Nominal duct width, delivery side | 600 mm |
| Degree of protection (IP) | IP41 |
| Explosion safety | None |
| Max. air temperature | 40 °C |
| Height | 1245 mm |
| Width | 869 mm |
| Length | 2400 mm |