Item number: 65125549
Pay safe and fast with:
The Maxivent HR air handling units with counterflow heat exchanger 2800 m3/h horizontal horizontal left - PHE 2800 H OOJL is a high-quality, robust, and advanced balanced ventilation unit with heat recovery, specifically designed for offices, clinics, and small to medium-sized commercial buildings. The air handling unit has a maximum airflow of 3570 m³/h and a thermal efficiency of 81%. The unit operates with a counterflow heat exchanger and EC fans, is designed for floor mounting, and features left-side access for maintenance.
The Maxivent HR air handling units with counterflow heat exchanger 2800 m3/h horizontal horizontal left - PHE 2800 H OOJL are developed for small to medium-sized commercial spaces such as offices, meeting rooms, clinics, retail stores, and educational or healthcare environments. Thanks to the combination of heat recovery and EC fans, the unit provides stable and energy-efficient ventilation. The integrated control and summer bypass ensure the indoor climate remains comfortable year-round, both during winter and hot periods.
Are you interested in a customised model and want to learn more about the possibilities? Please contact our sales department. They are happy to assist you in designing the ideal unit for your specific requirements.
| Brand | Maxivent |
| Category | Maxivent PHE Counterflow - Side Connection |
| GTIN | 8719544342430 |
| Manufacturer's item number | 78010747 |
| Article number | 78010747 |
| Category code | 36 |
| Length | 2400 mm |
| Width | 869 mm |
| Height | 1245 mm |
| Housing material | Steel |
| Heat recovery by | Counter current unit |
| Electrical connection | Terminals |
| Type of motor | Electronically commutated (EC) |
| Efficiency supply filter according to ISO 16890-1:2016 | 55 % |
| Degree of protection (IP) | IP41 |
| Efficiency exhaust filter according to ISO 16890-1:2016 | 50 % |
| With bypass | Yes |
| Supply filter according to ISO 16890-1:2016 | ISO ePM1 |
| Exhaust filter according to ISO 16890-1:2016 | ISO ePM10 |
| Connection voltage | 400 V |
| Surface protection housing | Continuously galvanised |
| External controller required | No |
| Device emplacement | Indoor positioning |
| With thermal overload protection | Yes |
| Type of speed control | Continuously variable |
| Air volume, unloaded | 2606.4 m³/h |
| Type of heating coil | None |
| Type of exhaust fan | Direct |
| Power consumption | 1.24 kW |
| Suitable for frequency control | No |
| Frost protection circuit | Yes |
| Pole-reversible | No |
| Explosion safety | None |
| Type of cooling coil | None |
| Suitable for transformer control | No |
| Suitable for electronic control | Yes |
| Type of supply fan | Direct |
| Max. air temperature | 40 °C |
| Change-over system | No |
| With humidifier | No |
| Nominal duct width of suction end | 600 mm |
| Connection suction side | Rectangular |
| Nominal duct width, delivery side | 600 mm |
| Number of connections delivery side | 2 |
| Nominal duct height of suction end | 400 mm |
| Connection delivery side | Rectangular |
| Nominal duct height, delivery side | 400 mm |
| Number of connections suction side | 2 |