- The largest collection in the United Kingdom
- 100 day return period
- Customer review 9/10
- Safe shopping with Trustedshops
Pay safe and fast with:
Good points
- Brand: Maxivent
- Heat exchanger compliant with EN 308 and Eurovent-certified
- Electric heating
- Plug & Play Integrated Controller
Maxivent WTW Air Handling Units with Counterflow Heat Exchanger 1700 m3/h with Right-side Electric Heater - PHE 1700 F EOJR
The Maxivent WTW air handling units with counterflow heat exchanger 1700 m3/h with right-side electric heater - PHE 1700 F EOJR are high-quality, robust, and advanced balanced ventilation systems with heat recovery, specially designed for offices, clinics, and small to medium-sized commercial buildings. The air handling unit offers a maximum airflow of 2060 m³/h and a thermal efficiency of 82%. The unit operates with a counterflow heat exchanger and EC fans and features an electric heater that ensures a stable and consistent supply air temperature while preventing frost formation in the heat exchanger. The air handling unit is designed for ceiling mounting and can be accessed from below for maintenance.
Benefits and Features
- Electric Heater: Integrated electric reheating prevents cold drafts and ensures a comfortable, stable supply air temperature without the need for a hot water connection.
- EC Fans: Direct-driven EC plug fans with high-efficiency electronic commutation (EC) provide an energy-efficient and quiet solution with low power consumption.
- Counterflow Heat Exchanger: The integrated, efficient counterflow heat exchanger recovers 82% of the thermal energy from the exhaust air without mixing air streams.
- Panel Filter F7/M5: Ensures a high level of filtration of dust particles and contaminants from outside air, contributing to a healthy and comfortable indoor climate and protecting internal components.
- Automatic Summer Bypass: Enables summer and night cooling by supplying cool outside air directly without warming it through the heat exchanger.
- Plug-and-Play Control: The air handling unit is delivered complete with built-in controls for all functions, allowing quick and easy installation and commissioning without additional control equipment.
Applications and Usage
The Maxivent WTW air handling units with counterflow heat exchanger 1700 m3/h with right-side electric heater - PHE 1700 F EOJR are designed for small to medium commercial spaces such as offices, meeting rooms, clinics, retail stores, and educational or healthcare environments. Thanks to the combination of heat recovery, EC fans, and electric heating, the unit provides stable and energy-efficient ventilation even at low outdoor temperatures. The integrated controls and summer bypass ensure a comfortable indoor climate year-round, both in winter and warmer periods.
Customising the WTW Unit
Are you interested in a customised model and would you like to know more about the options? Please contact our sales department. They will be happy to assist you and help configure the ideal unit tailored to your specific requirements.
| Brand | Maxivent |
| Category | Maxivent PHE Ceiling Units |
| GTIN | 8719544341082 |
| Manufacturer's item number | 78010612 |
| Article number | 78010612 |
Specifications
| Category code | 36 |
| Device emplacement | Indoor positioning |
| Housing material | Steel |
| Surface protection housing | Continuously galvanised |
| Air volume, unloaded | 1033.2 m³/h |
| Supply filter according to ISO 16890-1:2016 | ISO ePM1 |
| Efficiency supply filter according to ISO 16890-1:2016 | 55 % |
| Heat recovery by | Counter current unit |
| With bypass | Yes |
| Type of cooling coil | None |
| Type of heating coil | Electrical heating element |
| Change-over system | No |
| With humidifier | No |
| Type of supply fan | Direct |
| Exhaust filter according to ISO 16890-1:2016 | ISO ePM10 |
| Efficiency exhaust filter according to ISO 16890-1:2016 | 50 % |
| Type of exhaust fan | Direct |
| Connection voltage | 400 V |
| Power consumption | 1.04 kW |
| With thermal overload protection | Yes |
| Electrical connection | Terminals |
| Suitable for electronic control | Yes |
| Suitable for frequency control | No |
| Suitable for transformer control | No |
| Pole-reversible | No |
| External controller required | No |
| Frost protection circuit | Yes |
| Type of motor | Electronically commutated (EC) |
| Type of speed control | Continuously variable |
| Number of connections suction side | 2 |
| Connection suction side | Rectangular |
| Nominal duct height of suction end | 300 mm |
| Nominal duct width of suction end | 500 mm |
| Connection delivery side | Rectangular |
| Number of connections delivery side | 2 |
| Nominal duct height, delivery side | 300 mm |
| Nominal duct width, delivery side | 500 mm |
| Degree of protection (IP) | IP41 |
| Explosion safety | None |
| Max. air temperature | 40 °C |
| Height | 435 mm |
| Width | 1460 mm |
| Length | 1800 mm |