Item number: 78010470
Pay safe and fast with:
The Maxivent by Econox MR4565 unit is a highly efficient, robust, advanced, and versatile balanced ventilation system with heat recovery, specifically designed for educational institutions, theatres, and large-scale commercial buildings. With a nominal airflow of 6500 m³/h and a heat recovery rate exceeding 80%, this air handling unit is perfectly suited for your next commercial project where continuous ventilation without energy loss is essential. The unit operates using an efficient sorption wheel, EC fans, and an integrated control panel. Designed for floor mounting, the unit features handles on the right side for easy access and maintenance.
| Brand | Maxivent |
| Category | Maxivent MR45 heat recovery wheel - side connection |
| GTIN | 8719544340412 |
| Manufacturer's item number | 78010524 |
| Article number | 78010524 |
| Category code | 261 |
| Length | 2130 mm |
| Connection | Flange |
| Width | 1640 mm |
| Height | 1640 mm |
| Housing material | Steel, lined |
| Heat recovery by | Thermal wheel |
| Material heat exchanger | Aluminium |
| Max. air volume at 100 Pa | 6575 m³/h |
| Max. air volume at 200 Pa | 6750 m³/h |
| Electrical connection | Terminals |
| Type of motor | Electronically commutated (EC) |
| With constant pressure control | Yes |
| Efficiency supply filter according to ISO 16890-1:2016 | 50 % |
| Degree of protection (IP) | IP54 |
| Efficiency exhaust filter according to ISO 16890-1:2016 | 50 % |
| Max. air volume at 150 Pa | 6650 m³/h |
| Max. air volume at 50 Pa | 6500 m³/h |
| Max. air volume at 250 Pa | 6850 m³/h |
| With constant volume flow control | Yes |
| With bypass | No |
| Supply filter according to ISO 16890-1:2016 | ISO ePM1 |
| Exhaust filter according to ISO 16890-1:2016 | ISO ePM10 |
| Weight | 993 kg |
| Number of fan levels | 3 |
| Device emplacement | Indoor and outdoor positioning |
| With thermal overload protection | No |
| Max. air volume at 300 Pa | 6900 m³/h |
| Type of heating coil | Electrical heating element |
| Power consumption | 5.1 kW |
| Frost protection circuit | Yes |
| Type of cooling coil | Water/glycol |
| Suitable for transformer control | No |
| Suitable for electronic control | Yes |
| Connection voltage | 3x 400 V AC +N |
| Change-over system | Yes |
| Fan type | Direct |
| With condensate drain | Yes |
| With rotational speed/frequency control | Yes |
| With support frame | Yes |
| With roof plate | No |
| Suitable for low-current control | No |
| Thermal efficiency | 80 % |
| Max. air volume at 400 Pa | 6850 m³/h |
| Nominal duct width indoor connection | 1530 mm |
| Nominal duct height indoor connection | 710 mm |
| Max. air volume at 500 Pa | 6375 m³/h |
| Nominal duct height, outdoor connection | 710 mm |
| Max. air volume at 600 Pa | 5800 m³/h |
| Nominal duct width, outdoor connection | 1530 mm |
| Latent heat efficiency | 77 % |